Precision Digital PD6000 User Manual

Page 70

Advertising
background image

Model PD6000 Analog Input Process Meter Instruction Manual

70

Modbus RTU Serial Communications (serial)

The meter is equipped with serial communications capability as a stan-
dard feature using Modbus RTU Serial Communication Protocol.
To communicate with a computer or other data terminal equipment, an
RS-232 or RS-422/485 adapter option is required; see Ordering Infor-
mation
on page 7 for details.

Warning!

Do not connect any equipment other than Precision
Digital’s expansion modules, cables, or meters to the
RJ45 M-LINK connector. Otherwise damage will occur to
the equipment and the meter.

Note: More detailed instructions are provided with each optional serial

communications adapter.

Note: Refer to the PD6000/PD7000 Modbus Register Tables located at

www.predig.com for details.

baud

Serial

SlavId

Serial

tr dly

Serial

serial

t-byt

Serial

Parity

Serial


When using more than one meter in a multi-drop mode, each meter
must be provided with its own unique address. The meter address
(Slave ID) may be programmed between 1 and 247. The transmit delay
may be set between 0 and 199 ms. The parity can be set to even, odd,
or none with 1 or 2 stop bits.
The PD6000 can also be connected to another PD6000 with a special
PDA1200 cable, allowing the user to copy all the settings from one me-
ter to another, using the Copy function.