Model PD6000 Analog Input Process Meter Instruction Manual

89

Alphabetical List of Display Functions & Messages

Display Parameter

Action/Setting

Description

20 mA

20 mA output

Enter mA output value read by milliamp
meter with at least 0.001 mA resolution

4 mA

4 mA output

Enter mA output value read by milliamp
meter with at least 0.001 mA resolution

999999
-99999

Flashing
display

Overrange condition
Underrange condition

Ack

Acknowledge

Acknowledge relays

Act 1

Action 1

Set relay 1 action

Alm 1

Alarm 1

Assign digital output to Alarm 1-8

Altern

Alternate

Set relay for pump alternation control

A-man

Auto-manual

Set relay for automatic & manual reset

Aout

Analog output

Enter the Analog output scaling menu

Aoutpr

Analog output
programming

Enter analog output programming

Auto

Automatic

Press Enter to set automatic operation

baud

Baud rate

Select baud rate

big

Big display

Press Enter to assign the main display pa-
rameter (default: PV)

Big Hi

Max on big
display

Assign digital input to display max on the
main display

Big HL

Max/min big
display

Assign digital input to toggle max/min on the
main display

Big Lo

Min on big
display

Assign digital input to display min on the
main display

break

Loop break

Set relay condition if loop break detected

bypASs

Bypass

Set filter bypass value

C CAL

Current
calibration

Calibrate 4-20 mA current input (internal
reference source used for scaling the input)

C Hi

Current high

Calibrate high current input (e.g. 20 mA)

C lo

Current low

Calibrate low current input (e.g. 4 mA)

Cal

Calibrate

Enter the Calibration menu