Reset Meter to Factory Defaults

When the parameters have been changed in a way that is difficult to
determine what’s happening, it might be better to start the setup
process from the factory defaults.
Instructions to load factory defaults:
1. Enter

the

Advanced

Features menu. See Advanced Features

Menu, page 66.

2. Press Up arrow to go to Diagnostics menu
3. Press and hold Right arrow for five seconds, press

Enter when display flashes reset.
Note: If Enter is not pressed within three seconds, the display re-
turns to the Diagnostics menu.

4. The meter goes through an initialization sequence (similar as on

power-up), and loads the factory default settings.

996000

G P d

Run Mode

20.000

mA

reset

diaG

Press & hold Menu for

3 sec to access

Advanced features

Press & hold right

arrow for

3 sec to reset meter


Note: The dual-scale selection for level applications (LEVEL) is not re-

set to the single scale factory default. This can be changed using
the Setup – Input menu.