Model PD6000 Analog Input Process Meter Instruction Manual

79

Meter Copy Function (Copy)

The Copy function is used to copy (or clone) all the settings from one
meter to other meters requiring exactly the same setup and program-
ming (i.e. type of input, scaling, decimal point, filter, bypass, etc.).

Warning!

Only the PDA1200 meter copy cable must be used for
meter-to-meter interfacing. The PDA1200 is a special
eight-conductor flat cable with two wires swapped.
Using standard CAT5 or other cable will cause damage to
both meters.

Figure 19. Meter Copy Connection

Copy Function Requirements

To successfully copy settings from one
meter to another, both meters must have:

1. Same software version
2. Same baud rate setting

See Determining Software Version,

page 83 for instructions.

PDA1200 Meter Copy Cable