Model PD6210 & PD6310 Batch Controllers

Instruction Manual

44

Scaling and Calibration

It is very important to read the following information, before proceeding
to program the controller:

 There

is

no need to recalibrate

the controller when first received

from the factory.

 All inputs are factory calibrated. The calibration equipment used is

certified to NIST standards.

 Use

the

Scale

menu to enter the scaling without a signal source.

 Use

the

Calibrate

menu to apply a signal from a calibrator or a

flowmeter for the scaling.

Note:

The Scale and Calibrate functions are exclusive of each oth-

er. The controller uses the last function programmed. Only one of
these methods can be employed at a time. The Scale and Calibrate
functions can use up to 32 points (default is 2). The number of
points should be set in the Advanced menu under the Multi-Point Li-
nearization (Linear) menu selection prior to scaling or calibration of
the controller, see page 79 for details.