Model PD6210 & PD6310 Batch Controllers

Instruction Manual

49

Calibrating the Controller with External Source (Cal)

To scale the controller without a signal source refer to Scaling the

Controller (SCALE) page 47.

The controller can be calibrated to display the process variable in engi-
neering units by applying the appropriate input signal and following the
calibration procedure.
The use of a calibrated signal source is strongly recommended to cali-
brate the controller.

CAL

Prog

Inp 1

CAL

Inp 1

I n p 1

Inp 2

CAL

Inp 2

I n p 2

dis 1

Inp 1

00

0

.000

d i s 1

dis 2

Inp 2

1

00.000

d i s 2

The display

flashes while

sensing the

inputs

Warm up the controller for at least 15 minutes before performing

calibration to ensure specified accuracy.