Model PD6210 & PD6310 Batch Controllers

Instruction Manual

73

Function Keys Operation

During operation, the programmable function keys operate according to
the way they have been programmed in the Advanced Features – User
menu. The following table shows the default setting for each of the func-
tion keys.

Function Key/Button

Default Setting

Action

F1/START

Start

Start batch

F2/BATCH

preset

Change preset

F3/STOP

stop

Pause/stop batch

!

Only STOP Operation Enabled if a Batch is Running.

During a batch process, the only function that can be
performed is the pause/stop functions of the STOP button;
the default programming of the F3 key. No other functions,
including min/max display, manual alarm reset, or total
reset, will function while a batch is running.

Programmable Function Keys User Menu (user)


The User menu allows the user to assign the front panel function keys
F1, F2, F3 and up to eight digital inputs to access most of the menus or
to activate functions immediately (e.g. Reset max & min). Up to eight
digital outputs can be assigned to a number of actions and functions
executed by the controller (e.g. Alarms, relay acknowledgement, etc.).

user

dI 1

user

dO 8

user

dO 1

user

dI 8

user

F1

user

F3

user

F2

user

!

Changing the programming of the F1-F3 function keys will
disable the default batch operation of these keys, and is
not recommended for batch control applications.