Precision Digital PD6310 User Manual

Page 84

Advertising
background image

Model PD6210 & PD6310 Batch Controllers

Instruction Manual

84

Controller Copy Function (Copy)

The Copy function is used to copy (or clone) all the settings from one
controller to other controllers requiring exactly the same setup and pro-
gramming (i.e. type of input, scaling, decimal point, filter, bypass, etc.).

Warning!

Only the PDA1200 meter copy cable must be used for
meter-to-meter interfacing. The PDA1200 is a special
eight-conductor flat cable with two wires swapped.
Using standard CAT5 or other cable will cause dam-
age to both controllers.

Figure 22: Controller Copy Connection

Copy Function Requirements

To successfully copy settings from one controller to another, both
controllers must have:

1. Same

software

version

2. Same baud rate setting

See Determining Software Version, page 86 for instructions.

PDA1200 Controller Copy Cable

Advertising
This manual is related to the following products: