Linear, No pts, Scale – Precision Digital PD6310 User Manual

Page 79

Advertising
background image

Model PD6210 & PD6310 Batch Controllers

Instruction Manual

79

Square Root Linearization (Square)

The square root function can be used to linearize the signal from a diffe-
rential pressure transmitter and display flow rate in engineering units.

Programmable Exponent Linearization (Prog E)

The programmable exponent can be used to linearize the signal from
level transmitters in open-channel flow applications using weirs and
flumes.

Multi-Point Linearization (Linear)

Controllers are set up at the factory for linear function with 2-point linea-
rization. Up to 32 linearization points can be selected under the linear
function.

The multi-point linearization can be used to linearize the display

for non-linear signals such as those from level transmitters used to
measure volume in odd-shaped tanks or to convert level to flow using
weirs and flumes with complex exponent.

Program

Number of

Points

Linear

Functn

no Pts

Linear

scALE

Select

Low-Flow Cutoff (CutofF)

The low-flow cutoff feature allows the controller to be programmed so
that the often-unsteady output from a differential pressure transmitter, at
low flow rates, always displays zero on the controller.
The cutoff value may be programmed from 0 to 999999. The controller
will display zero below the cutoff value. Programming the cutoff value to
zero disables the cutoff feature.

Advertising