Model PD6210 & PD6310 Batch Controllers

Instruction Manual

82

6. Set the display value to correspond to the input signal being cali-

brated, typically 4.000 mA.

7. The display moves to the high input calibration (C Hi). Apply the

high input signal and press Enter.

8. Set the display for the high input calibration, in the same way as it

was set for the low input calibration, typically 20.000 mA.

C CAL

ICAL

C Lo

C CAL

C Hi

C CAL

0

04.000

C Lo

0

20.000

C Hi

The display

flashes while

sensing the

inputs

ICAL


The graphic above shows the calibration of the current input. The voltage
input is calibrated in a similar way.
Tips:

Low and high input signals can be any valid value within the
range of the controller.

Observe minimum input span requirements between input 1
and input 2.

Low input should be less than high input signal.