Model PD6210 & PD6310 Batch Controllers

Instruction Manual

48

Time Base, Total Conversion Factor & Total Reset

The time base, total conversion factor, and total reset menus are located
in the Program menu.
The total and grand total have their own independent settings. This
means that one can be displaying the value in gallons while the other
displays in million gallons, liters, m

3

, etc.

Batch Start Mode (mode)

The batch controller may operate in manual or automatic mode. In ma-
nual mode, the controller operates as defined in Controller Operation as
described on page 33. In automatic mode, the batch process will auto-
matically begin after a completed batch. The time delay for the restart
may be 0.1 to 999.9 seconds (t dly). Automatic batch start will only
occur after a successful batch. A manually stopped batch will require a
manual start to begin a new batch process.

Grand Total Reset

The grand total can be programmed for manual or automatic reset. In the
automatic reset mode, a programmable time delay is available to reset
the grand total after the assigned preset is reached.

Non-Resettable Totalizer

The total and grand total can be password-protected to prevent unautho-
rized resets. The grand total can be programmed as a non-resettable
total, see page 67 for details.