Model PD6210 & PD6310 Batch Controllers

Instruction Manual

46

Programming the Rate/Totalizer (prog)

It is very important to read the following information, before proceeding
to program the controller:
PD6210:

The PD6210 is factory calibrated prior to shipment to read in mil-
liamps and volts depending on the input selection. The calibration
equipment is certified to NIST standards.

 Use

the

Scale

menu to scale process inputs (e.g. 4-20 mA). A cali-

brated signal source is not needed to scale the controller.

PD6310

The PD6310 has been factory calibrated to read input frequency in
Hz (pulses/sec). The calibration equipment is certified to NIST stan-
dards.

Use the K-Factor menu to match the rate/totalizer with a flowmeter’s
k-factor (pulse/unit of measure).

Or use the Scale menu to scale the pulse input (pulse/sec) without a
signal source.

Or use Cal menu to calibrate the rate/totalizer using a signal source.


The Program menu contains the following menus:

1. Scale without a signal source
2. Calibrate with a calibrated signal source
3. Total time base & conversion factor
4. Grand total time base & conversion factor
5. Total reset mode for total & grand total

The process inputs may be calibrated or scaled to any display value
within the range of the controller.

p r o g

s C a l e

P r o g

C a l

P r o g

t C F

P r o g

t t b

P r o g

G ran d

T ot al

S e t t in gs

t r s t

P r o g

Additional parameters, not needed for most applications, are pro-
grammed in the Advanced Features menu; see ADVANCED OPERA-
TION AND PROGRAMMING, page 69.