Model PD6210 & PD6310 Batch Controllers

Instruction Manual

80

Analog Output Programming (AoutPr)

The Analog Output Programming menu is used to program the behavior
of the 4-20 mA output. The following parameters and functions are pro-
grammed in this menu:
1. Source: Source for generating the 4-20 mA output (e.g. PV)
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to

scale the 4-20 mA output

Analog Output Source

The source for generating the 4-20 mA output may be assigned to the
rate/process variable, total, grand total, maximum or minimum value
reached by the rate/process, or one of the set points, or the Modbus PV
input.

rate

Source

Source

AoutPr

Set Points

1 - 8

tot

Source

gtotal

Source

min

Source

max

Source

mbus

Source

Analog Output Calibration

To perform the analog output calibration it’s recommended to use a mil-
liamp meter with a resolution of at least 0.1 µA to measure the output
current. The values saved internally during this procedure are used for
scaling the 4-20 mA output in the Setup menu.