4/20/11

Heatilator • Constitution EPA Fireplace • 480-1091D

Page 39

7

Installation of Fireplace

This fireplace will operate correctly only if adequate ven-

tilation is provided to allow proper draft to the fireplace

system. See Section 6.
An outside air kit must be used for combustion to mini-

mize the effects of negative pressure within the structure.

We recommend you utilize the shortest duct run to opti-

mize the performance of the outside air kit. The outside

air kit inlet should be positioned in a manner that will not

allow snow, leaves, etc. to block the inlet. In some instal-

lations the air duct may need to be run vertically. In such

an installation, a 3 ft (914 mm) height difference must be

maintained from the top of the uppermost chimney sec-

tion to the outside combustion air inlet. See Figure 7.2

on page 40.
See Figure 7.1 for proper placement of outside air inlet.
The outside air kit is installed on the right hand side of the

fireplace. See Figure 7.3 for handle location/operation.

1. Cut a 6 in. (152 mm) hole in outside wall to accommodate

air piping. See Figure 7.3 on page 40.

2. Use 6 in. (152 mm) metal flex or rigid piping (not

supplied) to directly connect outside air to fireplace

intake. Insulate the pipe to prevent frost condensation.

3. Use the supplied termination cap.
4. Seal between the wall and the pipe with silicone to

prevent moisture penetration and air leaks.

5. Seal between the termination cap and the house with

silicone to prevent air infiltration.

NOTE: A control knob allows you control of the outside air

inlet. Use of outside air for combustion is required to

conserve heated air within the structure and to provide

make up air to keep the fireplace venting properly.

ImpORTANT! Outside air control considerations
Turn counter-clockwise to “OPEN” positions
Outside air knob must be in the “OPEN” position to oper-

ate fireplace properly.
May be closed when not in use to prevent cold air infiltra-

tion

CAUTION! Risk of Cuts/Abrasions. Wear protective

gloves and safety glasses during installation. Sheet metal

edges are sharp.

A. Install the Outside Air Kit

CAUTION! Risk of Fire or Asphyxiation! DO NOT draw outside combustion air from wall, floor or ceil-

ing cavity, or enclosed spaces such as an attic or garage.

DO NOT place outside air hood close to exhaust vents or chimneys. Fumes or odor could be drawn into the

room through the fireplace.

• Locate outside air inlet to prevent blockage from leaves, snow/ice, or other debris. Blockages could cause com-

bustion air starvation.

Outlet blocked by

snow, leaves, etc.

NO

Garage or

combustible

liquids storage

NO

Attic space

NO

Outlet placed

higher than 3 ft

below the

termination cap

NO

Use only duct materials

specified by manufacturer

Figure 7.1 Outside Combustion Air Placement