F. install ceiling firestops – Heatiator C40 User Manual

Page 46

Advertising
background image

Page 46

Heatilator • Constitution EPA Fireplace • 480-1091D

4/20/11

ROOM ABOVE (non-insulated ceiling)

ATTIC ABOVE (insulated ceiling)

B

A

Ceilng firestop

attached to bottom

of framing

Ceiling firestop

attached to top of

framing

When attic insulation

shield not used

Note:

Use same dimensional lumber for framing

ceiling firestop and joists.

2 in. (51mm)

clearance

2 in. (51mm)

clearance

Figure 8.7 Installing the Ceiling Firestop

Catalog #

A

B

in.

mm

in.

mm

FS338

14-1/2

368

14-1/2

368

FS339

14-1/2

368

18-3/8

467

FS340

14-1/2

368

23

584

Wire Ties

Wire Ties

4" Flex

Figure 8.6 Installing Flex Pipe

CAUTION! Risk of Fire! Ceiling firestops must be used

whenever the chimney penetrates a ceiling/floor.

Chase construction requires ceiling firestops at each floor

or every 10 ft (3.05 m) of clear space.

• The ceiling firestop slows spread of fire and reduces cold

air infiltration.

• Install a ceiling firestop whenever chimney penetrates

ceiling/floor.

• Mark and cut an opening in ceiling as shown in Figure 8.7.

• Frame the opening with the same size lumber used in

the ceiling joists.

• Nail the ceiling firestop to the bottom of the ceiling joists

when there is a room above.

• Use an attic insulation shield if the ceiling is insulated.

The ceiling firestop may then be attached above or below

the joists.

WARNING! Risk of Fire! DO NOT seal area between

firestop opening and chimney pipe except where they

enter the attic or leave the warm air envelope of the

home (use 600° F sealant).

F. Install Ceiling Firestops

Advertising