Heatilator • Constitution EPA Fireplace • 480-1091D

4/20/11

Install as per Sections 7 and 8.

• You MUST use a chase top in a chase installation. Chase

tops are available from your Heatilator dealer or may be

field constructed.

• Include a turndown and drip edge to prevent water from

seeping into the chase.

• Include a 2 in. (51 mm) soldered, welded or spun collar

around pipe opening to keep water out.

• Provide a 1/8 in. (3 mm) gap around the flue pipe.

• Slope the chase top downward away from the opening.
WARNING! Risk of Fire! DO NOT caulk the pipe to the

chase top collar.

• Caulk all seams to prevent leaks.

Slope Downward

(1/4 in. per foot

minimum)

Turn-down

Drip Edge

Chase

2 in. (51 mm) Collar

on Chase Top

.018 (26 ga) min.

Galvanized

Chase Top

Figure 9.3 Chase Top Construction

Install the chimney sections up through the chase enclo-

sure.

Caulk the overlap seam of any exposed pipe sections

that are located above the roof line to prevent leaks.

Refer to termination cap instructions.

WARNING! Risk of Fire! The minimum overlap of cap

to pipe (as shown in the following illustrations) MUST

be met or chimney may separate from cap. Separation

allows sparks, heat and embers to escape.

NOTICE: Paint the termination cap with a rust-resistant

paint to protect against the effects of corrosion on those

parts exposed to the weather.

• TR344 Round Termination Cap

Storm

Collar

Chimney

Pipe

Chase Top

Termination

Cap

Chase

6 in. (153 mm)

Minimum top of

chase to top of

chimney pipe

Collar

2 in. (51 mm)

Minimum Height

Do NOT

block air holes

Caulk gaps between

storm collar & pipe,

and storm collar

& chase top.

Termination cap pipe and chimney section must be snapped

together to maintain an overlap of 1-1/2 in. (38 mm).

Slip

storm collar

around chimney pipe

before termination

cap pipe is snapped

into the chimney

pipe.

Figure 9.4 Installing a TR344 Round Termination Cap

• TR342 Round Telescoping Termination Cap

Storm

Collar

Chimney

Pipe

Chase Top

Termination

Cap

Chase

14 1/2 in. (368 mm)

Maximum

Collar

2 in. (51 mm)

Minimum Height

Caulk gaps between

storm collar & pipe,

and storm collar

& chase top.

Do NOT

block air

holes

3 clip brackets.

Slip over chase collar

and attach with screws

provided.

Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)

Assemble

storm collar

around extended

termination cap

pipe

once cap is

installed.

Figure 9.5 Installing a TR342 Round Telescoping Termination Cap

D. Install Termination Cap

B. Install Fireplace & Chimney

C. Install Chase Top