Step 13 - setpoint sampling – Hach 900 MAX User Manual

Page 52

Advertising
background image

Page 50
Advanced Sampling

8990startup.fm

Section 3

Step 12 - Program Complete Output

Program Complete Output sends a +12 V dc signal out Pin F of the Auxiliary
Receptacle at the completion of the sampling program. This signal is also sent
when a Full Bottle condition causes the program to complete. The Program
Complete signal remains on (+12 V dc) for 61 seconds and then turns
back off (0 V dc).

Program Complete Output is used for the following purposes:

Multiple Sampler Operation. Samplers are arranged in a “Cascade”
control where the first sampler signals a second sampler to start its
program when the first sampler’s program is complete. This feature
requires the second sampler to be programmed for external
start operation.

To interface to a PC to signal the end of the sampling program.

To interface to a relay that trips a signal light in a control room to indicate
that sampling is finished and samples are ready to be picked up.

12-A. From the Advanced Sampling menu highlight Program Complete using

the

UP

and

DOWN

keys. Press

SELECT

to continue.

12-B. Enable or Disable Program Complete using the

CHANGE CHOICE

key.

12-C. Press

ACCEPT

to continue to Set Point Sampling.

Step 13 - Setpoint Sampling

Setpoint sampling allows the control of an automatic liquid sampler from one
of up to 14 sources. Setpoint sampling defines a set of limits that inhibit
sampling until an upset condition occurs, causing the limits to exceed.
Sampling is enabled only when the waste stream falls outside the setpoints.

13-A. Highlight Setpoint Sampling using the

UP

and

DOWN

keys on the

Advanced Sampling Menu. Press

SELECT

.

13-B. Enable or Disable Setpoint Sampling using the

CHANGE CHOICE

key.

Press

ACCEPT

to continue.

11:00 AM 21 - APR - 01

ADVANCED SAMPLING

SELECT

PGM CMPLT OUTPUT

RETURN

SETPOINT SAMPLING
SPECIAL OUTPUTS

11:00 AM 21 - APR - 01

ADVANCED SAMPLING

SELECT

PGM CMPLT OUTPUT

SETPOINT SAMPLING

RETURN

SPECIAL OUTPUTS
START/STOP TIMES

Advertising