3-30 TranSphere TS Wireless Extended Range IP Networking Transceivers – January 2008 GFK-2489

3

Remote Serial Gateway Configuration (IP-to-Remote Serial)

The Remote Serial Gateway Menu controls the IP encapsulation behavior of all Remote
radios. The gateway function is essentially a table with one entry for each Remote radio
passing serial data. No further configuration is required at Remote radios.

The AP can be configured to accept IP traffic to be exchanged with devices connected to the
serial ports of one or more Remotes. The screen below shows the starting point for
configuring the remote serial gateway settings.

Remote Serial Gateway Menu

A) RSG TalkBack Enable

enabled

B) RSG TalkBack Timeout

30 seconds

C) RSG Entries

D) Remote Serial Wizard



Select a letter to configure an item, <ESC> for prev menu

RSG Talkback Enable (UDP IP-to-Serial)

—When Talkback is enabled and the RSG is

set up for UDP mode, a message from a Remote radio (usually a reply to a poll) is sent to
the last IP address or port that a message was received from. [Enabled, Disabled;
Enabled]

RSG Talkback Timeout

—This selection is used to set a time limit after which, if no data

has been received from the IP host, the RSG talkback feature expires. When this
happens, the RSG reverts to its configured IP address and port for upstream data
destined for an IP host. [Time in seconds; 30]