Model MSX Make-Up Air

Installation Evaporative Cooler

Piping (optional)

IMPORTANT

All supply solenoids, valves and all traps must be below

the roof line or be otherwise protected from freezing.

IMPORTANT

The supply line should be of adequate size and

pressure to resupply the amount of water lost due to

bleed-off and evaporation. The drain line should be

the same size or larger than the supply line.

CAUTION

Provisions must be taken to prevent damage to the

evaporative cooling section during freezing conditions.

The sump, drain lines and supply lines must be

drained prior to freezing conditions or an alternate

method must be used to protect the lines and media.

Evaporative Cooling with Recirculating Pump

1. Install the Water Supply Line

Supply line opening requirements vary by unit size
and arrangement and are field supplied. Connect the
water supply line to the float valve through the supply
line opening in the evaporative cooling unit. Install a
manual shutoff valve in the supply line as shown.

2. Install the Drain Line

Connect an unobstructed drain line to the drain and
overflow connections on the evaporative cooler. A
manual shut off valve (by others) is required for the
evaporative cooler
drain line.
A trap should be
used to prevent
sewer gas from
being drawn into
the unit.

3. Check/Adjust Water Level

Check the water level in the sump tank. The water
level should be above the pump intake and below the
overflow. Adjust the float as needed to achieve the
proper water level.

Supply

Line

Overflow

Trap

Drain Line Valve

(Normally Open)

Drain Line

Supply

Line Valve

(Normally

Closed)

Recirculating Evaporative Piping

6 in. min.

6 in. min.

Drain Trap

Evaporative Cooling with Auto Drain and Fill

Auto Drain & Flush Valves

(When provided by Greenheck)

Assembly

Number

GFC

Part

Number

ASCO

Part

Number

Solenoid

Type

De-Energized

Position

Diameter Qty.

852178

461262 8210G2 Supply

Closed

1/2 inch

(12.7 mm)

1

461263 8262G262

Supply

Line

Drain

Open

1/4 inch

(6.35 mm)

1

461264 8210G35

Sump

Drain

Open

3/4 inch

(19.05 mm)

1

Part numbers subject to change.

IMPORTANT

The supply line should be of adequate size and
pressure to resupply the amount of water lost due to
bleed-off and evaporation. The drain line should be
the same size or larger than the supply line.

CAUTION

All solenoids valves and traps must be installed below
the roof to protect the supply water line from freezing.
If they cannot be installed below the roof, an alternative
method must be used to protect the lines from freezing.

IMPORTANT

The supply solenoid (Valve A) is NOT the same as
the drain solenoids (Valve B and Valve C). Make sure
to use the proper solenoid for each location. Check
your local code requirements for proper installation
of this type of system.

Auto Drain & Fill Evaporative Piping

Supply

Line

VALVE B

Supply Line Drain Solenoid

(Normally Open)

Sump Overflow

Sump Drain

VALVE C

Sump Drain Solenoid

(Normally Open)

VALVE A

Supply Solenoid

(Normally Closed)

Drain Line

Trap