Model MSX Make-Up Air

Water Wizard™ User Interface

Key Function Description

Function Key

Recommended Water Pressure Chart

Housing

Size

Media Width

(inches)

Water Pressure

(in. wc)

MSX-H12

30

20

MSX-H22

43

3

4

36

60

61

MSX-H32

66

72

96*

42

MSX-H35

120*

61

MSX-H38

180*

37

MSX-H42

216*

51

*Multiple media sections. Values represent total media width.

WARNING

Opening the manual supply valve will allow water

to pass to the media. Be sure the sump is safely

draining before opening the manual supply valve.

NOTE

The manual supply valve ships closed and must be

adjusted for proper performance.

NOTE

The recommended water pressure is based on

media width. Refer to the table provided for proper

water pressure settings.

Start-Up - Water Wizard™ (optional)

Program Display

NOTE

Steps 6 through 8 are provided to adjust the

minimum cooling temperature. The minimum cooling

is preset to the factory recommended 75°F (24°C).

Only adjust if needed.

NOTE

The inlet air sensor function overrides and shuts

down the evaporative cooler if the outside

temperature falls below the minimum cooling

temperature.

7. Adjust the Minimum Cooling
Temperature

While in the
Program Menu,
use the Up and
Down Keys to
navigate the
Menu Options
until “toF” is

displayed. Press the
Enter Key to access the selected Menu Option setting.
Use the Up and Down Keys to adjust the Minimum
Cooling Temperature as needed. Press the Enter Key
to save the Minimum Cooling Temperature setting and
return to the Program Menu.

8. Exit Program Mode

After 15 seconds of idle time the controller will exit
Program Mode.

Minimum Cooling

Temperature Display

NOTE

The enter key must be pressed to save the new

minimum cooling temperature.

5. Check Media

Start the cooling cycle and check the media after one
hour of operation. If the media is continuously dry or if
too much water is draining from the sump tank, refer
to Troubleshooting, Water Wizard™.

6. Enter Program Mode

Press and hold
the Enter Key

for three seconds. The
display will read “Pro”
when Program Mode is
active.

L1

L2

L3

Enter Key

Up Key

Down Key

1. Open the Solenoid

Confirm that the manual water supply valve
is closed. Press and hold the Function Button

for one second. L3 will begin blinking (short on, long
off), indicating that Flow Test Mode is active and the
supply solenoid is open.

2. Set the Water Pressure

With the solenoid open, set the supply water
pressure to the correct setting (see table below).

Use the manual supply valve to adjust the supply
pressure. A pressure gauge is provided between the
manual supply valve and the media.

3. Break-in Media

Leave the supply solenoid open to saturate and
break-in media for 20 minutes with the blower off.

4. Close Solenoid

With the pressure set, press the Function Key
for one second to deactivate Flow Test Mode

and allow the supply solenoid to close.