Set-up optional components, Air volume measurement & check – Greenheck Fan Make-Up Air Unit 470658 MSX User Manual

Page 17

Advertising
background image

17

®

Model MSX Make-Up Air

6. Set-Up Optional Components

Adjust the settings on the optional components. See
the Control Center Layout in the Reference section for
location of optional components.

• Heating Inlet Air Sensor

Typical setting: 60-70°F (15-21°C)

• Cooling Inlet Air Sensor

Typical setting: 75°F (24°C)

• Building Freeze Protection

Typical setting: 5 minutes; 45°F (7°C)

• Dirty Filter Gauge

Typical setting: Settings vary greatly for each unit.
(see Reference section for adjusting information)

NOTE

The most accurate way to measure the air volume is
by using a pitot traverse method downstream of the
blower. Other methods can be used but should be
proven and accurate.

IMPORTANT

Changing the air volume can significantly increase
the motor’s amps. If the air volume is changed,
the motor’s amps must be checked to prevent
overloading the motor.

NOTE

To ensure accuracy, the dampers are to be open
when measuring the air volume.

5. Air Volume Measurement & Check

Measure the unit’s air volume (cfm) and compare it with
it’s rated air volume. If the measured air volume is off,
adjust the fan’s RPM by changing/adjusting the drive.