35

®

Model MSX Make-Up Air

IMPORTANT

Be sure to read and follow the manufacturer’s

recommendations before using any cleaning fluid.

CAUTION

Caution should be used to avoid injury when venting

the coil. High pressure and/or high temperature

fluids can cause serious injuries.

Chilled Water Coils

Test the circulating fluid for sediment, corrosive
products and biological contaminants. Make the
necessary corrective measures.
Maintain adequate fluid velocities and proper filtering
of the fluid.
If automatic air vents are not utilized, periodic venting
of the coil is recommended to remove accumulated air.

Cooling Coils

Inspect the coil for signs of corrosion and/or leaks.
Repair any leaks as required.
Inspect the coil’s surface for foreign material. If the
coil surface needs cleaning, clean the coil from the
leaving air-side so that foreign material will be washed
out of the coil rather than pushed farther in.
Inspect and clean the drain pan to prevent the growth
of algae and other organisms.

Maintenance - Routine

continued

WARNING

Repair and replacement of the coil and the

connecting piping, valves, etc., should be performed

by a qualified individual.