Locate equipment support(s), Secure cooling module to unit, Set evaporative cooling module – Greenheck Fan Make-Up Air Unit 470658 MSX User Manual

Page 7: Apply sealant

Advertising
background image

7

®

Model MSX Make-Up Air

Installation of Evaporative Cooling

Module (optional)

NOTE

Small evaporative coolers ship attached to the base

unit and require no additional mounting.

NOTE

The use of all lifting lugs and a set of spreader bars is

mandatory when lifting the evaporative cooling module.

NOTE

When mounting the evaporative cooler, it is

important that it is level to ensure proper operation

and water drainage.

Metal Cover

Equipment

Support

Roof Curb

Equipment Support

Placing Evaporative Module

Securing Evaporative Module

1. Locate Equipment Support(s)

Position equipment support(s) on the roof (reference the
CAPS submittal for placement of equipment support(s)
in relation to the
unit). Verify that
all unit supports
are level, shim if
necessary. Attach
equipment support
to the roof, remove
metal cover, flash
to wooden nailer
and reinstall cover.

4. Secure Cooling Module to Unit

Use self-tapping screws to fasten the cooling module to
the base unit along the top and down both sides. Fasten
at the top through the flanges. To fasten the sides, the
media must be removed. To remove the media, first
remove the access panel on the evaporative module
and disconnect the evaporative pump(s). The media
will now slide out. With the media removed, you can
access the side fastening points inside the evaporative
module. With all the screws in place, reinstall the media,
reconnect the pumps and reinstall the access panel.

Sealant

3. Set Evaporative Cooling Module

Use a crane and a set of spreader bars hooked to the
factory lifting lugs to lift and center the module on the
equipment support(s). The flange on the evaporative
cooler should overlap the flange on the unit.

2. Apply Sealant

Apply an appropriate sealant around the airstream
opening to create an air tight seal.

Advertising