Model MSX Make-Up Air

Water Wizard™ — Improper Water Supply

Troubleshooting

1. Adjust the Manual Supply Valve

Adjust the manual supply valve (refer to Start-Up,
Water Wizard™). If the recommended water pressure
does not provide enough water, increase the pressure
until the desired water supply is achieved. If the
recommended water pressure provides too much
water, decrease the water pressure until the desired
water supply is achieved.

2. Enter Program Mode

Press and hold
the Enter key for

three seconds to enter
Program Mode. The
display will read “Pro”
when Program Mode is
active.

3. Adjust the On Time Factor

While in the Program Menu, use the Up and
Down keys to navigate through the menu
options until “ont” is displayed.
With “ont” displayed, press the Enter key to
access the setting.

With the setting displayed, use the Up and Down keys
to adjust the setting as needed.
Increase the factor to increase the water supply or
decrease the factor to decrease the water supply.
Press the Enter key to
save the new On Time
Factor and return to the
Program Menu.

NOTE

If the water supply is too low, the media will
continuously appear dry.

NOTE

If the water supply is too high, the media will be
saturated and excessive water will be draining from
the sump tank.

NOTE

Some water drainage is desired to keep the media
flushed, but it should be minimized to utilize the
Water Wizard™.

CAUTION

Only proceed to Steps 2 and 3 if Step 1 does not
correct the problem.

Program Display

On Time Factor Display

NOTE

Changing the On Time Factor by (1) will change the
water supply by approximately 3%.

IMPORTANT

The enter key must be pressed to save the new On
Time Factor.

4. Exit Program Mode

After 15 seconds of idle time the controller will
automatically exit Program Mode