Troubleshooting, Blower does not operate – Greenheck Fan Make-Up Air Unit 470658 MSX User Manual

Page 26

Advertising
background image

26

®

Model MSX Make-Up Air

Proper supply power at

main disconnect

Check main voltage

(See Blower Start-Up Step #1)

Main Disconnect (DS1) Off

(Turn Main Disconnect DS1 On)

Primary fuses blown

(Replace fuses)

24 VAC between

terminals R and X?

Main Transformer (TR1) Defective

(Replace transformer)

24 VAC between

terminals G and X?

Supply Switch (S2) Off

(Turn Supply Switch (S2) On)

Fire System Contact (FSC) tripped/not installed

(Correct/Replace)

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Blower Does Not Operate

Broken fan Bbelt

(Replace. Reference Maintenance section)

Defective motor or capacitor

(Repair/Replace)

Blown motor fuse

(Replace)

One or more legs of 3 phase is out

(Restore missing legs)

24 VAC across A2 and A1 on

supply contactor (ST1)

24 VAC across

terminals 4 and X?

24 VAC across

terminals 3 and X?

Supply Fan Overload (ST1 OL) tripped

(Reset and check motor amps. Reference Blower Start-Up #4)

Optional Exhaust Fan Interlocks (ST2-ST5) open

(Correct/Replace)

(Optional) Damper Limit Switch (DL1) holding

(Wait for actuator to open fully or adjust limit switch)

(Optional) Damper Limit Switch jumper missing

(Install jumper. Reference the unit’s ladder diagram for terminals)

Fan Relay (RF) is not energized

(Check for loose connection) (Repair or replace relay)

(Optional) Freeze Protection (RT4) Tripped

(Reset)

Troubleshooting

At this time the supply contactor (ST1) should pull in,

passing power to the supply motor

and the blower should start.