Troubleshooting, Electric heater does not operate (optional) – Greenheck Fan Make-Up Air Unit 470658 MSX User Manual

Page 30

Advertising
background image

30

®

Model MSX Make-Up Air

Electric Heater Does Not Operate (optional)

Supply fan must be on for heater to operate

Troubleshooting

24 VAC between

terminals W1 and X?

Heat Switch (S4) Off

(Turn Heat Switch (S4) On)

Heat Switch not wired

(Wire Heat Switch (S4))

24 VAC between

terminals 22 and 21?

Main Transformer (TR2) defective

(Replace transformer)

24 VAC between

terminals I and 21?

Pressure Differential Switch (PDS) open

(Check on cause of control loss)

Automatic and/or Manual Reset Cutouts (A and M) tripped

(Reset/Replace Automatic and/or Manual Reset Cutouts (A and M))

(Check on cause of control loss)

24 VAC between

terminals T1 and 21?

Heat Relay (RH) is not energized

(Check for loose connections). (Repair or replace Heat Relay (RH))

24 VAC between

terminal A2 on heat relay (RH)

and X?

(Optional) Inlet Air Sensor (TS4) holding

(Adjust (TS4) setting. Reference Blower Start-Up Step #6)

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

At this time the heater should be energized.

(The heating elements will not be on if the leaving air

temperature is above its set point on the Remote Adjuster (RA))