Mount pressure tap, Run pressure tap lines, Set the building pressure – Greenheck Fan Make-Up Air Unit 470658 MSX User Manual

Page 15

Advertising
background image

15

®

Model MSX Make-Up Air

Installation of Building Pressure

Control (optional)

1. Mount Pressure Tap

Using the factory provided bracket, mount the
pressure tap to the
outside of the unit.
Choose a location
out of the prevailing
winds and away from
supply or exhaust
fans to assure
accurate readings.

2. Run Pressure Tap Lines

Run a pressure tap line from the pressure tap on the
outside of the unit to the low pressure tap on the back
of the photohelic gauge. Run a second pressure tap
line from the high pressure tap on the back of the
photohelic gauge to the space. Fifty feet of tubing is
supplied with the unit.

3. Set the Building Pressure

The pressure gauge is used to set the desired building
pressure. The pressure is set by adjusting the knobs
for the upper and lower pressure limits. Typical
settings are 0.0 inch wc for the lower and 0.10 inch wc
for the upper pressure setting.

Connections for Photohelic Gauge

Factory

Wiring

High Pressure

Tap

to Space

Low Pressure

Tap

to Outside

Typical Photohelic Gauge Settings

Pressure Setting Knobs

Pressure Setting

Needles

Pressure Indicating

Needle