Greenheck Fan Make-Up Air Unit 470658 MSX User Manual

Page 21

Advertising
background image

21

®

Model MSX Make-Up Air

NOTE

The Freeze Temperature is preset to the factory

recommended 45°F. Steps 9-11 should only be

completed if the Freeze Temperature needs adjustment.

NOTE

The Freeze Temperature is the temperature at which the

supply solenoid closes and the drain solenoid opens

to drain the supply line, preventing possible freeze

damage. A drain solenoid is required for this option.

9. Enter Program Mode

Press and hold
the Enter Key

for three seconds. The
display will read “Pro”
when Program Mode is
active.

10. Adjust the Freeze Temperature

While in Program Mode, use the Up and Down
Keys to navigate
through the Menu
Options until
“Frt” is displayed.
Press the Enter
Key to access the

selected Menu Option
setting.
Use the Up and Down Keys to adjust the Freeze
Temperature setting as needed. Press the Enter Key to
set the Freeze Temperature and return to the Program
Menu.

11. Exit Program Mode

After 15 seconds of idle time the controller will exit
Program Mode.

Program Display

Freeze Temperature

Display

NOTE

The enter key must be pressed to save the new

freeze temperature.

Advertising