Operation - water wizard™ (optional) – Greenheck Fan Make-Up Air Unit 470658 MSX User Manual

Page 25

Advertising
background image

25

®

Model MSX Make-Up Air

Drain Mode

Drain Mode locks open the drain solenoid and drains
the supply line between the supply solenoid and
the media. To activate Drain Mode simultaneously,
press the Function and Enter Keys (L2 will light). To
deactivate Drain Mode and unlock the drain solenoid,
simultaneously press the Function and Enter Keys
again.

Flow Test Mode

Activating Flow Test Mode opens the supply solenoid
and allows water to pass to the manual supply
valve. To activate Flow Test Mode, press and hold
the Function Key for one second (L3 will flash). To
deactivate Flow Test Mode and allow the supply
solenoid to close, press and hold the Function Key
again for one second.

Program Mode

Program Mode allows the user to view the Program
Menu and edit the factory default settings. To access
Program Mode and view the Program Menu press and
hold the Enter key for three seconds. While viewing
the Program Menu press the Up and Down keys to
scroll through the Menu Options. To view the setting
of the selected Menu Option, press the Enter key.
To edit the setting, press the Up or Down key while
viewing the setting. To save the setting and return to
the Program Menu, press the Enter key. To return to
the Program Menu without saving the change, wait
10 seconds. To exit Program Mode from the Program
Menu, wait 10 seconds.

Function Key

L1

L2

L3

Enter Key

Up Key

Down Key

Water Wizard™ User Interface

Key Function Description

Operation - Water Wizard™ (optional)

CAUTION

The sump drain line must be clear and draining to a
safe location before using Flow Test Mode.

CAUTION

Be aware of the water level in the sump tank at all
times when using the Flow Test Mode.

WARNING

Changing the default settings will significantly affect
performance. Only change a setting after reading
and understanding this entire manual.

WARNING

The Enter key must be pressed to save any changes
made to a setting.

Dry Bulb Temperature

The dry bulb temperature is visible on the home
screen. If a number is not visible, wait 15 seconds
and use the Up and Down Keys until a number is
displayed.

Wet Bulb Temperature

To view the Wet Bulb Temperature, simultaneously
press and hold the Up and Down Keys.

Indicating Lights

Three indicating lights are located across the top
of the display to indicate the status of the Water
Wizard™.

Light Status

Indicating

Light

On

Off

Blinking

(Long on,

Short Off)

Blinking

(Short on,

Long Off)

L1

Call for

cooling

No call

for

cooling

Call for

cooling.

Outdoor

temperature

lockout.

N/A

L2

Drain

solenoid

open

Drain

solenoid

closed

N/A

Supply

solenoid

open.

(Drain

solenoid

closed).

L3

Cooling

on

Cooling

off

Supply

solenoid

locked
closed

Flow test

mode active

Advertising