Manitowoc Ice MARINE MODEL S1800 User Manual

Page 82

Advertising
background image

Refrigeration System

Section 7

7-16

Part Number 80-1634-3

DISCHARGE LINE TEMPERATURE ANALYSIS

General

Knowing if the discharge line temperature is increasing,
decreasing or remaining constant can be an important
diagnostic tool. Maximum compressor discharge line
temperature on a normally operating ice machine
steadily increases throughout the freeze cycle.
Comparing the temperatures over several cycles will
result in a consistent maximum discharge line
temperature.

Ambient air temperatures affect the maximum discharge
line temperature.

Higher ambient air temperatures at the condenser and/
or higher inlet water temperature = higher discharge line
temperatures at the compressor.

Lower ambient air temperatures at the condenser and/or
lower supply water temperature= lower discharge line
temperatures at the compressor.

Regardless of ambient and water temperatures, the
freeze cycle discharge line temperature will be higher
than 160°F (71.1°C) on a normally operating ice
machine.

Procedure

Connect a temperature probe on the compressor
discharge line with-in 6" of the compressor and insulate.

Observe the discharge line temperature for the last three
minutes of the freeze cycle and record the maximum
discharge line temperature.

Discharge Line Temperature Above 160°F (71.1°C) At

End Of Freeze Cycle:

Ice machines that are operating normally will have
consistent maximum discharge line temperatures above
160°F (71.1°C).

Discharge Line Temperature Below 160°F (71.1°C) At

End Of Freeze Cycle

Ice machines that have a flooding expansion valve will
have a maximum discharge line temperature that
decreases each cycle.

Verify the expansion valve sensing bulb is 100%
insulated and sealed airtight. Condenser air contacting
an incorrectly insulated sensing bulb will cause
overfeeding of the expansion valve.

Verify the expansion valve sensing bulb is positioned
and secured correctly.

Advertising