Refrigeration System

Section 7

7-20

Part Number 80-1634-3

Cycle Time/24 Hour Ice Production/

Refrigerant Pressure Charts

These charts are used as guidelines to verify correct ice
machine operation.

Accurate collection of data is essential to obtain the
correct diagnosis.

Refer to “OPERATIONAL ANALYSIS TABLE” for the
list of data that must be collected for refrigeration
diagnostics. This list includes: before beginning
service, ice production check, installation/visual
inspection, water system checklist, ice formation
pattern, safety limits, comparing evaporator inlet/
outlet temperatures, discharge and suction pressure
analysis.

Ice production checks that are within 10% of the
chart are considered normal. This is due to variances
in water and air temperature. Actual temperatures
will seldom match the chart exactly.

Zero out manifold gauge set before obtaining
pressure readings to avoid misdiagnosis.

Discharge and suction pressure are highest at the
beginning of the cycle. Suction pressure will drop
throughout the cycle. Verify the pressures are within
the range indicated.

Record beginning of freeze cycle suction pressure
one minute after water pump energizes.

Regular cube production derate is 7%

50Hz production derate is 7%

50Hz regular cube total production derate is 14%

S1800 SERIES

Self-Contained Water-Cooled

NOTE: These characteristics may vary depending on
operating conditions.

Cycle Times

Freeze Time + Harvest Time = Total Cycle Time

24 Hour Ice Production

Operating Pressures

Air Temp.

Around Ice

Machine

°F/°C

Freeze Time

Harvest

Time

Water Temperature °F/°C

50/10.0

70/21.1

90/32.2

70/21.1

8.5-9.4

9.2-10.1

10.7-11.8

.75-2.00

80/26.7

8.5-9.4

9.3-10.3

10.9-12.0

90/32.2

8.6-9.4

9.4-10.4

11.1-12.2

100/37.8

8.7-9.6

9.6-10.5

11.2-12.3

Times in minutes

Air Temp.

Around Ice

Machine

°F/°C

Water Temperature °F/°C

50/10.0

70/21.1

90/32.2

70/21.1

1870

1750

1530

80/26.7

1870

1730

1510

90/32.2

1860

1710

1490

100/37.8

1830

1690

1470

Based on average ice slab weight of 13- 14.125 lb

Condenser

Water

Consumption

Air Temperature / Water Temperature °F

77/59

90/70

110/90

Gal / per

100 lbs of ice

95

155

510

Water regulating valve set to maintain 240 PSIG discharge pressure

Air Temp.

Around Ice

Machine

°F/°C

Freeze Cycle

Harvest Cycle

Discharge

Pressure

PSIG

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Suction

Pressure

PSIG

50/10.0

225-235

40-24

140-160

60-80

70/21.1

225-275

45-26

155-175

60-85

80/26.7

230-295

45-28

160-180

70-90

90/32.2

255-320

46-29

170-195

80-100

100/37.8

290-360

48-30

190-215

95-115

110/43.3

325-400

49-30

225-250

110-130

Suction pressure drops gradually throughout the freeze cycle

Advertising