4-5. Connecting 3-Phase Input Power For 460/575 Volt Models

803 994-C

3/8 in

Tools Needed:

!

Installation must meet all National

and Local Codes − have only quali-

fied persons make this installation.

!

Disconnect and lockout/tagout in-

put power before connecting input

conductors from unit.

!

Make input power connections to

the welding power source first.

!

Always connect green or green/

yellow conductor to supply

grounding terminal first, and never

to a line terminal.

.

The circuitry in this unit automatically

adapts the power source to the

primary voltage being applied. Check

input voltage available at site. This

unit can be connected to either 460 or

575 VAC input power.

See rating label on unit and check input

voltage available at site.
1

Input Power Conductors (Customer

Supplied Cord)

Select size and length of conductors using

Section 4-4. Conductors must comply with

national, state, and local electrical codes.

If applicable, use lugs of proper amperage

capacity and correct hole size.
Welding Power Source Input Power

Connections
2

Strain Relief

Route conductors (cord) through strain re-

lief and tighten screws.
3

Machine Grounding Terminal

4

Green Or Green/Yellow Grounding

Conductor

Connect green or green/yellow grounding

conductor to welding power source

grounding terminal first.
5

Welding Power Source Line

Terminals

6

Input Conductors L1 (U), L2 (V) And

L3 (W)

Connect input conductors L1 (U), L2 (V)

and L3 (W) to welding power source line

terminals.
Close and secure access door on welding

power source.
Disconnect Device Input Power

Connections
7

Disconnect Device (switch shown in

OFF position)

8

Disconnect Device (Supply)

Grounding Terminal

Connect green or green/yellow grounding

conductor to disconnect device grounding

terminal first.
9

Disconnect Device Line Terminals

Connect input conductors L1 (U), L2 (V)

And L3 (W) to disconnect device line

terminals.
10 Over-Current Protection
Select type and size of over-current

protection using Section 4-4 (fused dis-

connect switch shown).
Close and secure door on line disconnect

device. Remove lockout/tagout device,

and place switch in the On position.

GND/PE Earth Ground

7

2

10

8

4

9

1

6

3

4

3

6

5