Determining External Regen Resistor Size, continued

Power
Dissipation
Calculation
Procedure
,
continued

Drive Energy
Absorption
Capability

The drive energy absorption capability values (in joules) that are needed during the
sizing calculations are provided in the following table.

Note: Multiple drives can be interconnected via the DC-Link. When this is done, the
energy absorption capability of the drives and the continuous power ratings of the
Regen resistors are additive. The energy absorbed by the drives must be
calculated by superimposing all the time speed plots and calculating the energy
generated by each axis. (For calculating the power in complex multi-drive
applications contact Schneider Electric for assistance.)

Step

Action

8

Compare the pulse power and the continuous power calculated with the
ratings of the internal Regen resistor in the drive. If either one is greater
then an optional external Regen resistor must be chosen and installed.
(See the Parts List appendix for a list of the available optional external
Regen resistors.)

Drive Energy Absorption Capability (joules)

Line Voltage

230 VAC

400 VAC

480 VAC

Drive
Model
Number

MHDS1004N00
MHDS1008N00
MHDS1017N00
MHDS1028N00

5

19

23

MHDS1056N00

10

38

47