Error
Identification
and Description
,
continued

Error
Code

Error (Fault)

Possible Cause/Corrective Action

F14

Drive output stage fault.

- Check motor cable for damage or shorts.

- Output module is overheated; improve ventilation.

- Short-circuit or short to ground in the external Regen
resistor.

- Motor has short-circuit/ground short; replace motor.

- Output stage is faulty; return drive to manufacturer.

F15

I²t maximum value
exceeded.

- I

rms

or I

peak

set incorrectly.

- Reduce motion profile duty cycle.

F16

Mains supply missing two
or three phases.

- Check mains fuses.

- Check mains wiring and connections on drive.

F17

A/D converter error.

Return drive to manufacturer

F18

Regen circuit faulty or
incorrect setting.

- Check jumper on X8 if using internal regen resitor.

- Check wiring of external regen resistor if used.

- Check fuses of external regen resistor.

F19

Mains supply missing one
phase.

- For single phase operation, set “Phase Missing”
parameter to “no message”.

- Check mains supply fuses.

- Check mains connector on drive.

- Check mains supply wiring.

F20

Slot fault

Hardware fault of the expansion card

F21

Handling fault

Software fault of the expansion card

F22

Reserved

Reserved

F23

Reserved

Reserved

F24

Reserved

Reserved

F25

Commutation error

Encoder system only