Troubleshooting, Problems, possible causes and corrective actions, Problem – Schneider Electric Lexium 17S Series User Manual

Page 93: Possible causes, Corrective actions, No communication with pc, Wrong cable used, Cable plugged into wrong position in drive or pc, Wrong pc interface selected, Check cable

Advertising
background image

81

Troubleshooting

Problems,
Possible Causes
and Corrective
Actions

The following table identifies some common system problems, their possible
causes and recommended corrective actions. However, the configuration of your
installation may create other reasons, and consequently other corrections, for the
problem.

Continued on next page

Problem

Possible Causes

Corrective Actions

No
communication
with PC

- Wrong cable used.

- Cable plugged into wrong
position in drive or PC.

- Wrong PC interface selected.

- Check cable.

- Plug cable into the correct
sockets on the drive and PC.

- Select correct interface.

Motor does not
rotate

- Drive not enabled.

- Break in SERCOS fiber optic
cable.

- Motor phases swapped.

- Brake not released.

- Motor is mechanically blocked.

- Motor pole number set
incorrectly.

- Feedback set up incorrectly.

- Apply enable signal

- Check cable

- Correct motor phase sequence

- Check brake control

- Check mechanism

- Set motor pole number.

- Set up feedback correctly.