Error Messages, continued

Error
Identification
and Description
,
continued

Continued on next page

Error
Code

Error (Fault)

Possible Cause/Corrective Action

F06

Motor overtemperature.

- I

rms

or I

peak

set too high.

- Defective motor

- If motor is not hot, check feedback cables and
connectors.

- Reduce motion profile duty cycle

- Improve ventilation of the motor

F07

Internal 24 Vdc fault.

Return drive to manufacturer

F08

Motor speed limit
exceeded.

- Feedback parameters not set correctly.

- Incorrect feedback wiring.

- Motor phases reversed.

- Check Parameter “Overspeed” for correct setting.

F09

EEPROM checksum error. Return drive to manufacturer.

F10

Flash-EPROM checksum
error.

Return drive to manufacturer.

F11

Motor brake fault.

- Brake parameter set to “WITH” when brake does not
exist.

- Defective brake.

- Check motor power cable and connections.

F12

Motor phase missing.

- Defective motor.

- Check motor power cable and connections

F13

Drive internal temperature
exceeded.

- Improve ventilation.

- Reduce motion profile duty cycle.

Advertising