Siemens CP 243-2 User Manual

Page 109

Advertising
background image

Command Interface

5-41

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

12

0

Parameter slave 12B

Parameter slave 13B

12

1

Parameter slave 14B

Parameter slave 15B

12

2

Parameter slave 16B

Parameter slave 17B

12

3

Parameter slave 18B

Parameter slave 19B

12

4

Parameter slave 20B

Parameter slave 21B

12

5

Parameter slave 22B

Parameter slave 23B

12

6

Parameter slave 24B

Parameter slave 25B

12

7

Parameter slave 26B

Parameter slave 27B

12

8

Parameter slave 28B

Parameter slave 29B

12

9

Parameter slave 30B

Parameter slave 31B

12

10

Flag 1

12

11

Flag 2

Flag 1

Flag 2

Bit Number

Meaning

Bit Number

Meaning

0

OFFLINE_READY

0

OFFLINE

1

APF

1

INTERNAL

2

NORMAL_MODE

2

EEPROM_OK

3

CONFIG_MODE

3

AUTO_ADDR_ENABLE

4

AUTO_ADDR_AVAIL

4

PERIPHERY_FAULT

5

AUTO_ADDR_ASSI_GN

5

reserved

6

LDS_0

6

reserved

7

CONFIG_OK

7

MPO startup

Flags whose values modify the AS-i master mode are shown on a gray
background.

The values of the other flags have no significance for the ’store total configuration’
command and cannot be modified on the AS-i master with this call.

Only the gray shaded flags can be modified.

CONFIG_MODE

The entry ‘0’ means that the CP 243-2 changes to the protected mode after
executing the command. The entry ‘1’ means that the CP continues in the
configuration mode.

0

The AS-i master starts up in the protected mode
on completion of the job.

1

The AS-i master starts up in the configuration mode
on completion of the job.

AUTO_ADDR_ENABLE

’0’ means that the automatic address programming is disabled, ’1’ means
that the automatic address programming is enabled.

0

Automatic address programming disabled.

1

Address programming enabled.

Advertising