background image

Command Interface

5-12

SIMATIC NET CP 243-2 AS-i Master

C79000-G8976-C142/02

General Structure of the AS-i Slave Address

If an AS-i slave is addressed in a command or in a reply, the address is structured
as shown below:

Bit 7

Bit 5 Bit 4

Bit 3

Bit 0

S bit

Slave address

Where the S(elect) bit for selecting the slave type is specified as follows:

S

S bit = 0
Standard AS-i slave or AS-i slave with extended addressing mode in address
area A

S

S bit = 1
AS-i slave with extended addressing mode in address area B