Siemens CP 243-2 User Manual

Page 132

Advertising
background image

Dealing with Problems / Error Displays

6-4

SIMATIC NET CP 243-2 AS-i Master

C79000-G8976-C142/02

Table 6-1

Error Displays of the CP 243-2 / Remedying Errors

Error

Remedy

Possible Cause

The CP 243-2 does not switch
from the configuration mode to the
protected mode.

The S7-200 CPU is in the “RUN”
mode.

Switch the S7-200 CPU to
“STOP”. This sets the PLC_RUN
bit to 0.

The SET button was not pressed
long enough.

Press the button for at least 0.5
seconds.

A slave with address “0” is con-
nected to the AS-Interface cable.
The CP 243-2 cannot change to
the protected mode as long as
this slave exists.

Remove the slave with
address 0.

The CP 243-2 does not switch
from the protected mode to the
configuration mode.

The S7-200 CPU is in the “RUN”
mode.

Switch the S7-200 CPU to
“STOP”.
This sets the
PLC_RUN bit to ‘0’.

Button not pressed long enough

Press the button for at least 0.5
seconds.

After failure of an AS-Interface
slave, the “AUP” display remains
off.

The CP 243-2 is in the configura-
tion mode.

“Automatic programming” is not
possible in the configuration
mode.
Program the address of the new
AS-Interface slave with the ad-
dressing unit.

More than one AS-Interface slave
has failed.

Check the AS-Interface cable.
If “APF” is displayed at the same
time, check the power supply on
the AS-Interface cable.
If more than one AS-Interface
slave is defective, program the ad-
dress on the replaced AS-Inter-
face slaves using the addressing
unit.

The CP 243-2 has not detected
configured AS-Interface slaves.

Remove the unconfigured AS-In-
terface slaves from the AS-Inter-
face cable.

The AUTO_ADDR_ENABLE flag
is not set.

Set the bit with the appropriate
commands or by pressing the
SET button during AS-i Power
Fail.