Command Interface

5-4

SIMATIC NET CP 243-2 AS-i Master

C79000-G8976-C142/02

A command started by the CP 243-2 is executed completely regardless of the
state of the ASI_COM bit.

The ASI_RESP bit is only reset by the CP 243-2 when the user program has set
the ASI_COM bit to “0”.

Example

The following example in STL applies to a CPU 222 with a CP 243-2 plugged in
directly beside it:

The example shows the sequence of the Read_Lists_and_Flags command.
Command execution is triggered by the positive edge at input 0.0.

To simplify matters, 224 bytes are always transferred to the CP 243-2 in these
examples. When the response is read in from the CP 243-2, 224 bytes are also
transferred. This allows each command to be processed regardless of its length.

Table 5-1

OB1 (STL)

NETWORK 1
LD SM0.1

//If: bit “First Scan”:

SI Q1.7, 1

//PLC_RUN = 1

RI Q.0, 6

//select bank 0

LD I1.1

//If: CP_READY

MOVW 16#3000, VW700

//Enter code “Read_extended_lists”

CALL 3

//Then: SBR 3

Table 5-2

SBR 3 (STL)

NETWORK 1

//Transfer the command data

LD I0.0

//If trigger bit

EU

//pos. edge

AN Q1.6

//ASI_COM

AN I1.6

//ASI_RESP

RI Q1.0, 6

//Select bank 2

SI Q1.1, 1

//Select bank 2

BMW VW700, AQW0, 8

//V memory –> bank

SI Q1.0, 1

//Select bank 3

BMW VW716, AQW0, 8

//V memory –> bank

RI Q1.0, 2

//Select bank 4

SI Q1.2, 1

//Select bank 4

BMW VW732, AQW0, 8

//V memory –> bank