Dealing with Problems / Error Displays

6-5

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

Table 6-1

Error Displays of the CP 243-2 / Remedying Errors

Error

Remedy

Possible Cause

Automatic address programming
is unsuccessful although the
“AUP” display is lit.

The configuration data (I/O confi-
guration, ID codes) of the repla-
ced AS-Interface slave do not
match the values of the original
AS-Interface slave.

Check whether the correct “repla-
cement slave” was used.
Compare the information from the
manufacturer about configuration
data.
If you want to replace the original
AS-Interface slave with a different
type, assign the address with the
addressing unit and reconfigure
the CP 243-2 (for example by
pressing the SET button).

The replaced AS-Interface slave
does not have the address “0”.0

Set the address of the replaced
AS-Interface slave with the ad-
dressing unit.

Replaced AS-Interface slave is
not correctly connected or is de-
fective.

Check the connections of the AS-
Interface slave and if necessary
replace the AS-Interface slave.

The “CER” LED and the LEDs of
active AS-Interface slaves flicker
irregularly.

An extender is installed in the AS-
Interface with “Line1” and “Line2”
connections reversed.

Correct the connections to the ex-
tender.