Command Interface

5-22

SIMATIC NET CP 243-2 AS-i Master

C79000-G8976-C142/02

5.2.10

Set_Extended_LPS

Purpose

With this call, the list of configured AS-i slaves is transferred for permanent storage
in the EEPROM.

When this command is executed, the AS-i master changes to the offline phase and
then changes back to the normal mode (warm restart on the AS-i master).

The call is not executed in the protected mode.

Structure of the Job Data in the Send Buffer

Bank

Byte

Meaning

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

2

0

29

H

2

1

00

H

2

2

slave 0

slave 1

slave 2

slave 3

slave 4

slave 5

slave 6

slave 7

2

3

slave 8

slave 9

slave 10

slave 11

slave 12

slave 13

slave 14

slave 15

2

4

slave 16

slave 17

slave 18

slave 19

slave 20

slave 21

slave 22

slave 23

2

5

slave 24

slave 25

slave 26

slave 27

slave 28

slave 29

slave 30

slave 31

2

6

reserv.

slave 1B

slave 2B

slave 3B

slave 4B

slave 5B

slave 6B

slave 7B

2

7

slave 8B

slave 9B

slave

10B

slave

11B

slave

12B

slave

13B

slave

14B

slave

15B

2

8

slave

16B

slave

17B

slave

18B

slave

19B

slave

20B

slave

21B

slave

22B

slave

23B

2

9

slave

24B

slave

25B

slave

26B

slave

27B

slave

28B

slave

29B

slave

30B

slave

31B

In the LPS data, 0 means AS-i slave not configured, 1 means AS-i slave
configured.

Structure of the Job Data in the Receive Buffer

Bank

Byte

Meaning

2

0

Echo of the command number: 29

H

2

1

Command status