Technical Description and Installation Instructions

1-16

SIMATIC NET CP 243-2 AS-i Master

C79000-G8976-C142/02

1.9

Configuring the AS-Interface with the SET Button

Interpreting the Display Status

The CP 243-2 distinguishes between two operating modes on the AS-Interface:

S

Configuration mode

S

Protected mode

Pressing the SET button changes the operating mode.

Note

The SET button is only effective when the bit PLC_RUN

=

0 is set in the control

byte of the CP 243-2. This is always the case when the S7-22x CPU is in the
STOP mode.

Configuration Mode

The configuration mode is used to install and start up an AS-i installation.

If the CP 243-2 is in the configuration mode (CM LED lit), it can exchange data
with every AS-i slave connected to the AS-i cable (except for an AS-i slave with
address ’0’). Newly added AS-i slaves are detected immediately by the master,
activated, and included in cyclic data exchange.

When installation and startup is completed, the CP 243-2 can be switched to the
protected mode using the SET button. At the same time, active AS-i slaves are
configured. The following data are then stored permanently on the CP 243-2:

S

The addresses of the AS-i slaves

S

The ID codes (ID code,

extended ID1 code, extended ID2 code

)

S

The I/O configuration

S

The current slave parameters

Protected Mode

In the protected mode, the CP 243-2 exchanges data only with the configured AS-i
slaves. In this sense, “configured” means that the slave addresses and the
configuration data stored on the CP 243-2 match the values of existing AS-i slaves.