Access to the Data of the AS-i Slaves

3-3

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

Assignment of the AS-i Input Data of the Standard or A Slaves (Bank 0 in the
Analog Input Area of the CP)

Bank Byte no.

Bit 7–4

Bit 3–0

0

m+0

reserved

Slave 1 or slave 1A

Bit 3 | Bit 2 | Bit 1 | Bit 0

0

m+1

Slave 2 or slave 2A

Slave 3 or slave 3A

0

m+2

Slave 4 or slave 4A

Slave 5 or slave 5A

0

m+3

Slave 6 or slave 6A

Slave 7 or slave 7A

0

m+4

Slave 8 or slave 8A

Slave 9 or slave 9A

0

m+5

Slave 10 or slave 10A

Slave 11 or slave 11A

0

m+6

Slave 12 or slave 12A

Slave 13 or slave 13A

0

m+7

Slave 14 or slave 14A

Slave 15 or slave 15A

0

m+8

Slave 16 or slave 16A

Slave 17 or slave 17A

0

m+9

Slave 18 or slave 18A

Slave 19 or slave 19A

0

m+10

Slave 20 or slave 20A

Slave 21 or slave 21A

0

m+11

Slave 22 or slave 22A

Slave 23 or slave 23A

0

m+12

Slave 24 or slave 24A

Slave 25 or slave 25A

0

m+13

Slave 26 or slave 26A

Slave 27 or slave 27A

0

m+14

Slave 28 or slave 28A

Slave 29 or slave 29A

0

m+15

Slave 30 or slave 30A

Bit 3 | Bit 2 | Bit 1 | Bit 0

Slave 31 or slave 31A

Bit 3 | Bit 2 | Bit 1 | Bit 0

m = start address of the CP analog module in the input direction

Assignment of the AS-i Output Data of the Standard or A Slaves (Bank 0 in the
Analog Output Area of the CP)

Bank Byte no.

Bit 7–4

Bit 3–0

0

n+0

reserved

Slave 1 or slave 1A

Bit 3 | Bit 2 | Bit 1 | Bit 0

0

n+1

Slave 2 or slave 2A

Slave 3 or slave 3A

0

n+2

Slave 4 or slave 4A

Slave 5 or slave 5A

0

n+3

Slave 6 or slave 6A

Slave 7 or slave 7A

0

n+4

Slave 8 or slave 8A

Slave 9 or slave 9A

0

n+5

Slave 10 or slave 10A

Slave 11 or slave 11A

0

n+6

Slave 12 or slave 12A

Slave 13 or slave 13A

0

n+7

Slave 14 or slave 14A

Slave 15 or slave 15A

0

n+8

Slave 16 or slave 16A

Slave 17 or slave 17A

0

n+9

Slave 18 or slave 18A

Slave 19 or slave 19A

0

n+10

Slave 20 or slave 20A

Slave 21 or slave 21A

0

n+11

Slave 22 or slave 22A

Slave 23 or slave 23A

0

n+12

Slave 24 or slave 24A

Slave 25 or slave 25A

0

n+13

Slave 26 or slave 26A

Slave 27 or slave 27A

0

n+14

Slave 28 or slave 28A

Slave 29 or slave 29A

0

n+15

Slave 30 or slave 30A

Bit 3 | Bit 2 | Bit 1 | Bit 0

Slave 31 or slave 31A

Bit 3 | Bit 2 | Bit 1 | Bit 0

n = start address of the CP analog module in the output direction