Siemens CP 243-2 User Manual

Page 131

Advertising
background image

Dealing with Problems / Error Displays

6-3

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

6.2

Error Displays of the CP 243-2 / Remedying Errors

<F 1>The following table lists the possible causes of errors that can occur when
operating the CP 243-2 and how to remedy the problem.

Table 6-1

Error Displays of the CP 243-2 / Remedying Errors

Error

Possible Cause

Remedy

APF LED lit

The AS-Interface power supply
unit is not connected or is defec-
tive.

Check the connection of the AS-
Interface power supply unit; if ne-
cessary replace the power supply
unit.

Power requirements of the AS-In-
terface slaves are too high. Re-
sult: The voltage on the AS-Inter-
face cable is too low.

Check the power requirements of
the AS-Interface slaves. If neces-
sary, supply the slaves with power
externally.

Short-circuit on the AS-Interface
cable.

Check the AS-Interface cable and
the attached slaves.

SF lights up without pressing the
SET button.

The CP 243-2 is defective. Inter-
nal EEPROM error.

Replace the CP 243-2.

SF is lit when the SET button is
pressed.

An AS-Interface slave with ad-
dress 0 exists when there is a
change to the protected mode.

Remove the slave with address 0
from the AS-Interface cable.

CER is lit permanently.

The CP 243-2 has not yet been
configured.

Configure the CP 243-2 using the
mode button on the front panel.

A configured AS-Interface slave
has failed (evaluate the slave dis-
play).

Replace the defective AS-Inter-
face slave or configure the
CP 243-2 again if the slave is not
required.

An unconfigured AS-Interface
slave was connected to the AS-In-
terface cable.

Remove the AS-Interface slave or
reconfigure the CP 243-2 .

An AS-Interface slave was con-
nected whose configuration data
(I/O configuration, ID codes) do
not match the values of the confi-
gured AS-Interface slave.

Check whether the wrong AS-In-
terface slave has been connec-
ted. If necessary, reconfigure the
CP 243-2.

CER display flickers, in other
words a configured AS-Interface
slave is lost sporadically.

Bad electrical connection.

Check the electrical connections
of the AS-Interface slaves.

Noise affecting the AS-Interface
cable.

Check the correct grounding of
the S7-200 and check the AS-In-
terface cable. Check that the
shield of the AS-Interface power
supply unit is connected correctly.

Advertising