Command Interface

5-20

SIMATIC NET CP 243-2 AS-i Master

C79000-G8976-C142/02

5.2.8

Store_Actual_Configuration

Purpose of the Command

With this call, the (actual) configuration data (I/O configuration, ID code, extended
ID1 code and extended ID2 code) of all AS-i slaves are stored permanently in the
EEPROM as the (expected) configuration data. The list of activated AS-i slaves
(LAS) is adopted in the list of permanent AS-i slaves (LPS).

When this command is executed, the AS-i master changes to the offline phase and
then changes back to the normal mode (warm restart on the AS-i master).

The call is not executed in the protected mode.

Structure of the Job Data in the Send Buffer

Bank

Byte

Meaning

2

0

Command number: 07

H

Structure of the Job Data in the Receive Buffer

Bank

Byte

Meaning

2

0

Echo of the command number: 07

H

2

1

Command status