9 get_extended_actual_configuration – Siemens CP 243-2 User Manual

Page 89

Advertising
background image

Command Interface

5-21

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

5.2.9

Get_Extended_Actual_Configuration

Purpose of the Command

With this call, the following configuration data of an addressed AS-i slave obtained
by the AS-i master on the AS-Interface are read.

S

I/O configuration

S

ID code

S

Extended ID1 code

S

Extended ID2 code

The configuration data are specified by the manufacturer of the AS-i slave. The
meaning of the configuration data is described in /2/.

Structure of the Job Data in the Send Buffer

Bank

Byte

Meaning

Bit 7

Bit 4

Bit 3

Bit 0

2

0

Command number 28

H

2

1

Slave address

Structure of the Job Data in the Receive Buffer

Bank

Byte

Meaning

Bit 7

Bit 4

Bit 3

Bit 0

2

0

Echo of the command number: 28

H

2

1

Command status

2

2

ID code

I/O configuration

2

3

Extended ID1 code

Extended ID2 code