3 meaning of the data in the digital module – Siemens CP 243-2 User Manual
Page 33
Advertising
![background image](/manuals/144217/33/background.png)
Interface to the User Program in the S7-200 CPU
2-7
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
2.3
Meaning of the Data in the Digital Module
Overview
The digital module of the CP 243-2 consists of four registers:
S
Identification register, 8 bits (I/O module identifier)
S
Error register, 8 bits
S
Input register 8DI (status byte of the CP 243-2)
S
Output register 8DO (control byte of the CP 243-2)
Essentially, the functions shown in the following diagram are handled via these
registers:
CP 243-2
User program
Digital module (8DI/8DO)
Analog module (8AI/8AO)
S7-200 CPU
НН
НН
НН
НН
НН
НН
ОО
ОО
ОО
ОО
ОО
ОО
AS-i master
AS-i cable
S
Status/error information
S
Control of the CP
S
Bank selection
Figure 2-2
Advertising