Command Interface

5-43

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

5.2.19

Write_Extended_Parameter_List

Purpose

With this command, the parameters for all slaves are transferred to the CP 243-2.
The CP 243-2 transfers only the parameters that have changed, in other words
that deviate from the current actual parameters
to the AS-i slaves.

Structure of the Job Data in the Send Buffer

Bank

Byte

Meaning

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

2

0

Command number 3C

H

2

1

00

H

2

2

irrelevant

Parameters slave 1

2

3

Parameters slave 2

Parameters slave 3

2

4

Parameters slave 4

Parameters slave 5

2

5

Parameters slave 6

Parameters slave 7

2

6

Parameters slave 8

Parameters slave 9

2

7

Parameters slave 10

Parameters slave 11

2

8

Parameters slave 12

Parameters slave 13

2

9

Parameters slave 14

Parameters slave 15

2

10

Parameters slave 16

Parameters slave 17

2

11

Parameters slave 18

Parameters slave 19

2

12

Parameters slave 20

Parameters slave 21

2

13

Parameters slave 22

Parameters slave 23

2

14

Parameters slave 24

Parameters slave 25

2

15

Parameters slave 26

Parameters slave 27

3

0

Parameters slave 28

Parameters slave 29

3

1

Parameters slave 30

Parameters slave 31

3

2

irrelevant

Parameters slave 1B

3

3

Parameters slave 2B

Parameters slave 3B

3

4

Parameters slave 4B

Parameters slave 5B

3

5

Parameters slave 6B

Parameters slave 7B

3

6

Parameters slave 8B

Parameters slave 9B

3

7

Parameters slave 10B

Parameters slave 11B

3

8

Parameters slave 12B

Parameters slave 13B

3

9

Parameters slave 14B

Parameters slave 15B

3

10

Parameters slave 16B

Parameters slave 17B

3

11

Parameters slave 18B

Parameters slave 19B

3

12

Parameters slave 20B

Parameters slave 21B

3

13

Parameters slave 22B

Parameters slave 23B

3

14

Parameters slave 24B

Parameters slave 25B

3

15

Parameters slave 26B

Parameters slave 27B

4

0

Parameters slave 28B

Parameters slave 29B

4

1

Parameters slave 30B

Parameters slave 31B