Command Interface

5-11

SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02

Command Status

Whether or not the job was executed correctly or errors occurred is signaled in the
command status of the response buffer in byte 1.

Table 5-6

Value

Meaning

00

H

Job completed without error

81

H

The AS-i slave address is incorrect

82

H

The AS-i slave is not activated (not in LAS).

83

H

Error on AS-Interface.

84

H

Command not permitted in the current status of the AS-i master.

85

H

An AS-i slave with address 0 exists.

86

H

The AS-i slave has illegal configuration data (I/O or ID codes).

A1

H

The addressed AS-i slave was not found on the AS-Interface.

A2

H

An AS-i slave with address 0 exists.

A3

H

An AS-i slave with the new address already exists on the AS-Interface.

A4

H

The AS-i slave address cannot be deleted.

A5

H

The AS-i slave address cannot be set.

A6

H

The AS-i slave address cannot be stored permanently.

A7

H

Error reading the extended ID1 code.

A8

H

The target address is not plausible (for example a B slave address was
used for a standard slave).

B1

H

A length error has occurred transferring a string according to profile 7.4.

B2

H

A protocol error has occurred transferring a string according to profile
7.4.

F8

H

The job number or the job parameter is unknown.

F9

H

The AS-i master has detected an EEPROM error.